UPS System

ED Series

Description

·

NEW TECHNOLOGY
Three level rectifier & inverter
High and stable online efficiency (up to 96%)
High input PF (≥0.99)
Low input current THD (<4%)
High output PF (0.9)
Low output voltage THD (<2%)
Short response time (<2ms)
High input and output performance

 

 

Technical Details

POWER  Rated Power Sn(KVA)│160 │200 │350 │
Pn(KW ) │144 │180 │315 │
INPUT Voltage 380 / 400 / 415 Vac 3ph N
Voltage tolerances ± 15% (without downgrading)
Frequency 50 / 60 Hz
Frequency tolerances
± 10%

 

Power factor ≥ 0.99
THDi < 4%
BYPASS Dual input Standard
Voltage 380 / 400 / 415 Vac 3ph N
Voltage tolerances ± 10% (adjustable)
Frequency 50 / 60 Hz
Frequency tolerances adjustable up to ± 10%
OUTPUT Voltage 380 / 400 / 415 Vac 3ph N
Voltage tolerances ± 1% (static load), dynamic load in accordance with VFI-SS-11
Frequency 50 / 60 Hz (selectable)
Frequency tolerances ± 0.1% (self-synchronize), ± 4% (mains-synchronize, adjustable up to ± 5%)
Power factor 0.9
THDv ≤ 2% (linear load), ≤ 5% (non-linear load)
Crest factor 3:1
OVERLOAD CAPACITY 110% 30 min.
125% 5 min.
150% 30 sec.
> 150% Bypass mode continuously
EFFICIENCY (online) 25% load 95.2
50% load 96.0
75% load 95.8
100% load 95.3
Eco-mode up to 98%
GENERAL Technology True online-double conversion, Three level rectifier & inverter
Control DSP, SPWM
Battery quantity of a group (12V) 60/64
Communication SNMP, RS232, RS485, MODBUS
Remote monitoring SNMPView, UPSMon, Remote panel
Dry contacts Programmable 7 dry contacts
Custom inputs Generator, Battery temperature sensor, Remote EPO
ENVIRONMENT Operating temperature from 0 °C up to 40 °C (from 20 °C to 25 °C for maximum battery life)
Relative humidity 0% - 85% (without condensation)
Maximum altitude 1000 m (without downgrading), max. 2000 m
Noise level < 65 dB (A)
Paralleling units up to 6
UPS CABINET Dimensions (W x D x H) (mm) 780 x 960 x 1850 780 x 1260 x 1850
Weight (kg) 600 640 750
Degree of protection IP20
Colour RAL7012
BATTERY CABINET Cabinet no. 5 6 7 8 9 10 11 12 13 14 15 16
Battery quantity (max.) 64 64 64 64 64 32 60 32 64 32 60 32
Battery capacity (Ah) 18 26 30-33-35 38-40-45 55 65 60-75-80 90-100 120
STANDARDS Certificates EN 62040-1 (Safety), EN 62040-2 (EMC)
UPS LIFETIME 10 years